TM 10-4130-237-14
1-8.
DIFFERENCES BETWEEN MODELS (CONT)
d. Centrifugal Clutch. Some water chillers (designated as Model LCC2685) are equipped with a centrifugal clutch
and matching compressor pulley to reduce starting load and delay period between starts. Differences in repair or adjust-
ment are listed in the appropriate maintenance procedures.
1-9.
MOUNTING KITS. There are two different mounting kits with the water chiller. Differences in repair are listed
in the appropriate maintenance procedure.
1-10.
EQUIPMENT
Water Chiller
Height, cover .
Width, cover .
Length, cover .
Height, overall
Width, overall
Length, overall
Gross weight .
Engine
Type . . . . . . . .
Model series . .
Horsepower . . .
DATA
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Spark plug (resistor type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Crankcase oil capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Purpose Kits
Support kit
Gross weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trailer mounting kit
Gross weight (less packing) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping Container
Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
With . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20in. (51cm)
25in. (64cm)
29in. (74cm)
24in. (61cm)
26in. (66cm)
34in. (86cm)
315 lb (143 kg)
2-cylinder
422435
1
8
106 lb (48 kg)
gap 0.030 in. (0.76 mm)
3.5 pt ( 1.7 liters)
47 lb (21 kg)
69 lb (31 kg)
41 in. (104 cm)
32 in. (81 cm)
45 in. (114 cm)
679 lb (308 kg)
Section III. PRINCIPLES OF OPERATION
1-11.
GENERAL OPERATION. The water chiller consists of an air-cooled, gasoline engine, a refrigeration system,
and a water system. The refrigeration system processes refrigerant through an evaporator. The water system circulates
water through the evaporator which absorbs the watcrs heat. The engine turns drivebelts. These belts drive the compressor
and water pump.
1-4