4.22
Figure 4-10 shows maximum and minimum spacings between these accumulators and the vessel structure.
4.23
Either one or two accumulators may be connected to a single 3/4" pipeline.
4.24
The coverage of a single accumulator is a circle of 40 ft. radius.
4.25
If a single space is larger than that which may be covered by two accumulators, one or more additional lines must
be used.
4.26
In case of very small spaces, (less than 5,000 cu. ft. (141.58m3), a maximum of 3 accumulators may be used on
a single detection zone.
4.27
There is no limitation on the height of the protected space.
4-10