TM 10-4610-237-12
4.16 GATE VALVE. ASSEMBLY (2-INCH) RFPAIR - Continued.
(11)
Apply anti-seize tape to threads of male coupling (3). Using pipe wrench, screw coupling (3) into valve body
(13).
(12)
Install gasket (3B) into cap (3A).
(13)
Secure cap (3A) to male coupling (3) using ring (3C).
(14)
Install gate valve assembly in water system (para 3.4a).
(15)
Startup water system (para 2.9c) and check valve assembly for leaks. If valve leaks at stem (11), tighten
packing nut (6) 1/4 turn until leak stops. Do not over tighten.
Figure 4-7. Gate Valve Assembly (2-Inch) Repair
4-30 Change 1