TM 10-4610-243-13
2-10.
ASSEMBLY AND PREPERATION FOR USE - cont.
g.
Assemble Interconnection Kits.
Two interconnection kits are supplied with the water system. One kit is
installed between dual tank connection kits 2 and 3 and the other between kits 6 and 7.
WARNING
To prevent contamination of drinking water, do not remove caps and plugs from
components until couplings are ready to be connected.
NOTE
Each interconnection kit is supplied with ten, 20 foot discharge hoses. This manual
reflects a typical water system installation. Install the number of hoses required to
meet your installation requirements.
All couplings in the interconnection kit are 4-inch diameter.
Assemble interconnection kit between dual tank connection kits 2 and 3.Refer to figure 2 -14, sheet 1.
(1)
Disconnect 10 foot discharge hose (2) from 20 foot discharge hose (1).
(2)
Connect tee (3) to 20 foot discharge hose (1).
(3)
Connect 10 foot discharge hose (2) to tee (3).
(4)
Connect four 20 foot discharge hoses (4, 5, 6, and 7) to tee (3).
(6)
Disconnect 10 foot discharge hose (10) from 20 foot discharge hose (9).
(7)
Connect tee (8) to 20 foot discharge hose(9).
(8)
Connect end of 10 foot discharge hose (10) to tee (8).
(9)
Connect end of 20 foot discharge hose (9) to tee (8).
Assemble interconnection kit between dual tank connection kits 6 and 7 Refer to figure 2-14, sheet 2.
(10)
Repeat steps (1) through (9) for other interconnection kit.
2-40