TEST OF REGULATOR EXCITER ASSEMBLIESTESTING AND ADJUSTINGTEST OF REGULATOR EXCITER ASSEMBLIES(Regulator Removed From Generator)FABRICATED TOOLING - FT1488The special fabricated tooling ( FT1488) provides a wayto test the power generator regulator - exciterassemblies. It allows testing after repairs withoutconnecting to the generator set.TEST PROCEDURE1.PreparationA.Connect regulator-exciter to the FT tester asdirected by connection chart.CONNECTION CHARTTesterTerminal12345678SR-4Terminal5624262220F1F2B.Set voltage, droop and gain controls full CCW.C.Set tester variac control CCW.D.Turn power switch on.2.Relay TestA.Turn the variac slowly CW. at 90 ± 20 volts,there should be slight drop in the field voltage asthe relay energizes.3.Level control testA.Set voltage level control to mid-range position.B.Increase the variac position, raise general.voltage, until the field voltage starts to decreaseand the load lamp starts to dim. This conditionshould occur between 200 and 260 volts on thegenerator voltmeter.C.Turn the voltage level control CW. the fieldvoltage should increase and the load lampshould brighten.D.Turn the voltage level control CCW. the fieldvoltage should decrease and the load lampshould dim.4.Gain control testA.Set variac, generator voltmeter. to '240 volts.B.Adjust level control till load lamp is dim.C.Turn gain control CW. load lamp brightnessshould increase, field voltage should Increase.5.Droop control testA.Set gain control CCW.B.Set variac, generator voltmeter, to 240.C.Adjust level control till load lamp is dim.D.Turn droop control CW, load lamp should go out,field voltage should decrease.NOTE: If the load lamp gets brighter and fieldvoltage increases, reverse the secondary leads oftransformer T3. This should only occur the first timethe tester is used.75
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business