Generator Lubrication and MaintenanceBRUSH CONTACTSPRINGMINIMUMAREATENSIONLENGTHInchmmOunceGramInchmm5/8 x 5/1616 x 8144009/16147/8 x 5/1622 x 8205509/161411/8 x 1/228 x 134011003/419a. If spring tension is less than shown in the chart: Pushthe spring forward one notch in the retainer clip. Checkthe spring tension.b. If the spring tension is greater than shown in thechart: Release the spring by one notch. Check thespring tension.c. If the spring tension is less than shown in the chartand the spring is in the forward notch, remove the brushand check the brush length.Removing and Installing Brushes - SRCR Only1. Release the spring from the retainer.3. Remove and inspect the brush. If the brush length isless than the minimum shown or if badly pitted, install anew brush.2. Disconnect the lead wire of the brush.4. Connect the lead wire of the brush.5. Place the brush in the brush holder. Be sure thebrush moves freely in the holder.6. Cut a strip of "00" sandpaper the width of the brush.Never use emery cloth for this purpose. Emery containssmall metallic particles which can damage the copperrings.22