PAGE 6b.Connections:1)Connect B+ to terminals 12, 18, 20.2)Connect B- to terminal 11.3)Connect engine crank solenoid to terminal 20 and B-.4)Connect engine run solenoid (or governor control B+ terminal) to terminal 19 and B-.5)Connect low oil pressure shut-down signal to terminal 14. The OPR relay contact from terminal 14 to9 closes 15 to 45 seconds after engine runs.6)Connect low oil pressure warning signal (when used) to terminal 16. The OPR relay contact fromterminal 16 to 15 closes 15 to 45 seconds after engine run.7)Connect crank cut-out to terminal 13 either positive or negative, 8) Connect all engine failure signalsto terminal 10. All signals must be of the same polarity either positive or negative. When used inconjunction with an LM-4 Light Module, the common failure output on the LM-4 provides this signal tothe Autostart.9)For single light Autostart operation, connect the common failure light to terminal 29 and B+. Commonfailure juniper "F" must be in place for dingle light operation, (see jumper selection below).10)Terminal 30 goes to ground in reset (off) position of engine control switch. This signal is used to resetthe Light Module.11)Connect the engine control switch as shown:Terminal 33 is a regulated 8 volt supply.Terminal 32 arms the engine failure lockout and the remote start contact.Terminal 31 will start cranking the engine to run by the manual switch or the remote startcontact.c.Jumper Selection:1)Voltage Jumper:This jumper is located directly behind terminal 8 and is marked "V". When this jumper is inplace the system is ready to operate at 12 to 24 VDC. When clipped out the system is ready tooperate at 32 VDC.2)Re-Crank Jumper:This jumper is red insulated and located next to the large 2200 MFD capacitor and marked "C".When in place the system can be manually re-cranked immediately after an engine shut downsignal. When clipped out the system will re-crank only after a 20 second time delay after anengine shut down signal. Re-crank delay is always in effect, independent of jumper, when theengine control switch is in the automatic position.
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business