PAGE 9CF 1, 2, 3, 4 RED INSULATED JUMPER. When in place the Light Module will signal common fault atterminal 5. When clipped out the corresponding input signal will not signal the common fault atterminal 5.A 1, 2, 3, 4 YELLOW INSULATED JUMPER. When in place the horn will sound on thatcorresponding signal input. When clipped out the horn will not sound when the corresponding signalappears.LAMP TEST JUMPER MARKED "T". When in place, terminal 27 is a B+ voltage for the lights andhorn. When clipped out a lamp test switch can be connected from terminal 27 to B- for simultaneoustest of all lamps connected to the module.VOLTAGE JUMPER MARKED "V". When in place the Light Module will operate at 12 to 24 VDC.When clipped out the Light Module will operate at 32 VDC.d.The Complete Engine Control System (Autostart And Light Module): All connections shown in the diagrambelow are described in Articles A & B of this section.