ELECTRICAL EQUIPMENTQ.15
9.
Unhook the plunger spring (14) from the sliding
plunger (11).
10.
Take off the moving contact plate, remove the
contact spring (42).
11.
Remove both solenoid and main terminals (46)
and (47) from the end-shield.
12.
Unscrew the three solenoid end-plate fixing
screws (49), (53) and (56). Take out the
endplate
(43)
complete
with
the
solenoid
housing. If the plate offers resistance, screw in
two 2BA screws, (approx. 2 in (50 mm) long)
one into the trip gear fixing hole, the other into
the stop-plate fixing hole. The end plate may
then be easily extracted.
Under no circumstances should the solenoid
windings and resistor assembly be disturbed
or any damage done to the mica housing.
REPAIR AND TESTING INSTRUCTIONS
COMMUTATOR
Examine commutator for wear which, if not severely
pitted or grooved can be cleaned up with fine glass or
carborundum paper (do not use emery cloth), whilst
spun in a lathe. If however, the commutator is badly
worn it should be skimmed, taking a very light cut, if
possible with a diamond tool to provide the desired high
quality finish.
The commutator insulating segments must not be
undercut.
ARMATURE COILS
The respective armature coils can be tested for
continuity or short circuits by mounting the armature
between centres and connecting the commutator to an
ordinary battery through the medium of two brass or
copper brushes mounted at an angle of 90° to each
other. Contact is then made to any two adjacent
commutator bars by means of hand spikes which are
connected direct to a milli-volt meter.
A variable resistance should be included in the battery
circuit capable of carrying the full output of the battery
and adjusted to give 2 volts or less on the armature.
The armature is then rotated until every commutator bar
has been tested, the reading on the milli-volt meter in
each case should
read
approximately
the
same;
any
big
variation,
indicating a fault in the coil connected to one of the
commutator bars under test. A reduction in the milli-volt
reading will be generally found due to a short circuit
while an increased reading will indicate either an open
circuit or a faulty connection.
In the event of an armature being found to be faulty, it
should be returned direct to a C.A.V. Agent.
ARMATURE SHAFT
Examine the elliptical recesses in the armature shaft
for burrs caused by the steel balls and carefully file these
off. Finally inspect the helices for any signs of damage.
Thoroughly clean with a suitable cleaning fluid and lightly
oil using Cal tex Thuben 90 or SAE 90 oil.
FIELD COILS
These can be simply tested when in position for short
circuits to the yoke and poles by means (of hand spikes
connected to a mains supply and in series with a lamp of
suitable voltage positioned on the live side of the
system. One spike should be applied to the end of the
winding and the other to the yoke. If the lamp does not
light then insulation is intact. Take care to remove all
other connections to the coils and insulate bare ends.
There is no easy way of testing internal shorts in the
coils as the resistance is very low ; new coils should be
tried if existing ones are suspect.
BEARINGS
If either the commutator or drive end bearings are
worn and need replacing, proceed as follows:
(a)
Commutator End Bearing
1.
Press the old bearing bush out of the end shield.
2.
Press the new bearing into the end shield by
using a stepped highly polished mandrel. A
special fitting pin, with a dimension of 0.6263 in
0.0002 in (15,908 0,005 mm), is supplied by the
makers. After assembly, the bore should be
within the limits 0.6258 in to 0.6268 in (15,895 to
15,921 mm). No machining should be
attempted.
Note
Before fitting a new bearing bush it
should be completely immersed for
24 hours in clean thin engine oil.