SR 4 GENERATOR
SYSTEMS OPERATION
D REGULATOR ADJUSTMENT
GENERATOR VOLTAGE ADJUSTMENT CONTROLS
4. Voltage droop control. 5. Voltage level control.
6. Regulator gain control.
Adjustment of voltage level rheostat (R2) is done with
voltage level control (5). This is done when an increase
or decrease of the generator voltage is necessary to get
correct line voltage. Adjustment of regulator gain
rheostat (R3) is done with regulator gain control (6).
Adjustment of regulator gain rheostat (R3) and voltage
level rheostat (R2) must be made in sequence to get
exact generator voltage regulation when the engine is
equipped with either a mechanical speed droop or an
isochronous (0% speed droop) governor. Do the steps
that follow:
1.
Remove the access panel on the left side of the
generator. Loosen the locknuts on the voltage
adjustment controls. Turn voltage droop control
(4) fully counterclockwise.
2.
Start the engine. Increase engine speed to
nameplate rating.
3.
Adjust voltage level control (5) to give nameplate
rated voltage. Put a normal load on the
generator. Let the generator warm up to normal
temperature for operation.
4.
Remove the load from the generator. Adjust the
voltage level control if necessary. Put a normal
load on the generator. Check generator voltage.
If the voltage stays at nameplate rating,
regulator gain control (6) is adjusted correctly.
Tighten all locknuts.
5.
If generator VOLTAGE INCREASES, turn the
regulator
gain
control
a
small
amount
counterclockwise.
If
generator
VOLTAGE
DECREASES, turn the regulator gain control a
small amount clockwise. Remove the load.
Adjust the voltage level control if necessary.
6.
Put a normal load on the generator. If the
voltage does not stay at nameplate. rating see
Step 5. If it does, tighten all locknuts and install
the access panel.
NOTE
Generator sets equipped with a
control panel on top of the generator
have the voltage level rheostat in the
control panel. The yellow wire from
terminal 7 on the terminal strip of the
regulator assembly is disconnected.
The voltage level rheostat on the
control panel is then connected to
terminals 6 and 7 on the terminal
strip.
The
same
sequence
of
adjustments must be made.
In order to get an even distribution of reactive load and
to keep circulating currents to a minimum when two or
more generators are operated in parallel. it is necessary
to have a specific decrease in voltage, at each
generator, with an increase in generator load. This
decrease in voltage is the voltage droop. Adjustment of
voltage droop potentiometer (R1) is done with voltage
droop control (4). Correction to the voltage droop can be
made by turning (R1) from counterclockwise for no
voltage droop to clockwise for an increase In voltage
droop. Adjustment of voltage droop control (4) must be
in sequence with voltage level control (5) and regulator
gain control (6). See OPERATION GUIDE for engine.
42