INSTALLATIONINSTRUCTIONSFORMODELMBC8&MBC9BATTERYCHARGERS(Continued)TABLE1-LOWERCHASSISTERMINALSTRIPWIRING(Cont'd)TERMINALMINIMUMWIRESIZE(COPPER)DESIGNATIONDK1, DK2-- #24 AWG --Crank Disconnect Relay Input Terminals-Connect toa source of DC voltage equivalent to the Chargernominal DC voltage rating, when battery is supplyinghigh current loads such as engine cranking or switchgear operation to prevent overloading the Charger.Coil resistance-800 ohms on 12 volt Chargers and3,200 ohms on 24 volt units.TABLE2BATTERYMINIMUMWIRESIZES(COPPERWIRE)CHARGERWITHOUTREMOTESENSEWITHREMOTESENSERated D.C.Max WireMin WireTotal LoopMin WireTotal LoopCurrentRun LengthSizeDropSizeDrop10 FT16 AWG0.2V16 AWG0.2V2 1/2 AMP25 FT16 AWG0.5V16 AWG0.5V50 FT14 AWG0.6V16 AWG1.0V10 FT16 AWG0.4V16 AWG0.4V5 AMP25 FT14 AWG0.6V14 AWG0.6V50 FT12 AWG0.8V14 AWG1.2V10 FT12 AWG0.3V12 AWG0.3V10 AMP25 FT12 AWG0.8V12 AWG0.8V50 FT8AWG0.6V10 AWG1.0V10 FT10 AWG0.4V10 AWG0.4V20 AMP25 FT8AWG0.6V10 AWG1.0V50 FT6AWG0.8V8AWG1.2VNote that while the wire size shown for the AC wiring is based on wire current carrying capacity ('ampacity'), thewire sizes shown for the battery wiring are based on wiring resistance. In addition, splices or junctions in thewiring path must be low in resistance.Runs may be two of the next smaller even wire size, e.g. two #12 AWG wires may be used in place of a #10 AWG wire,etc. Aluminum wire NOT recommended.MBC8/9(10000)-3-2-