INSTALLATION INSTRUCTIONS FOR MODEL MBC8 & MBC9 BATTERY CHARGERS
(Continued)
TABLE 1 - LOWER CHASSIS TERMINAL STRIP WIRING (Cont'd)
TERMINAL
MINIMUM WIRE SIZE (COPPER)
DESIGNATION
DK1, DK2
-- #24 AWG --
Crank Disconnect Relay Input Terminals-Connect to
a source of DC voltage equivalent to the Charger
nominal DC voltage rating, when battery is supplying
high current loads such as engine cranking or switch
gear operation to prevent overloading the Charger.
Coil resistance-800 ohms on 12 volt Chargers and
3,200 ohms on 24 volt units.
TABLE 2
BATTERY MINIMUM WIRE SIZES (COPPER WIRE)
CHARGER
WITHOUT REMOTE SENSE
WITH REMOTE SENSE
Rated D.C.
Max Wire
Min Wire
Total Loop
Min Wire
Total Loop
Current
Run Length
Size
Drop
Size
Drop
10 FT
16 AWG
0.2V
16 AWG
0.2V
2 1/2 AMP
25 FT
16 AWG
0.5V
16 AWG
0.5V
50 FT
14 AWG
0.6V
16 AWG
1.0V
10 FT
16 AWG
0.4V
16 AWG
0.4V
5 AMP
25 FT
14 AWG
0.6V
14 AWG
0.6V
50 FT
12 AWG
0.8V
14 AWG
1.2V
10 FT
12 AWG
0.3V
12 AWG
0.3V
10 AMP
25 FT
12 AWG
0.8V
12 AWG
0.8V
50 FT
8
AWG
0.6V
10 AWG
1.0V
10 FT
10 AWG
0.4V
10 AWG
0.4V
20 AMP
25 FT
8
AWG
0.6V
10 AWG
1.0V
50 FT
6
AWG
0.8V
8
AWG
1.2V
Note that while the wire size shown for the AC wiring is based on wire current carrying capacity ('ampacity'), the
wire sizes shown for the battery wiring are based on wiring resistance. In addition, splices or junctions in the
wiring path must be low in resistance.
Runs may be two of the next smaller even wire size, e.g. two #12 AWG wires may be used in place of a #10 AWG wire,
etc. Aluminum wire NOT recommended.
MBC8/9(10000)-3
-2-