THEORYOFOPERATIONMODELMBC8BATTERYCHARGER(continued)CRANKDISCONNECT- The crank disconnect relay is supplied by the 'DK' terminals. This reed relay shunts the SCRpulse transformer input when operated which prevents SCR turn on.SHUTDOWN- The shutdown sense line (SD) is connected to the internal SCR trigger drive signal on the regulator boardthrough a diode. The 'SD' line does not input current and will not discharge the battery on power outage. Thus with ashorted output, the load will "Steal" the SCR trigger drive signal (via terminal +B), preventing SCR turn on, to shutdownthe Charger.MBC8(10003) iss2Page 2 of 2