SR 4 GENERATORSYSTEMS OPERATIONMANUAL VOLTAGE CONTROL ATTACHMENTThe location of the manual voltage control panel canbe up to 76 ft. (23.2 meters) from the generator. Makereference to the chart.CONTROLPANEL LOCATIONWIRE SIZE (AWG)MAXIMUM CABLE LENGTHNo. 1830 ft. (9.1 meters)No. 1648 ft. (14.6 meters)No. 1476 ft. (23.2 meters)The manual voltage control can be used to controlgenerator voltage when there is a failure in the generatorregulator assembly. It will manually control the rate atwhich control rectifier CR9 is turned on. For informationon CR9 operation make reference to OPERATION OFGENERATOR.NOTE: CR9 and CR10 must be able tooperate correctly for the manual voltagecontrol to work.The manual voltage control has a switch (1), voltagecontrol rheostat (2), flash button (3) and a controlassembly.VOLTAGE CONTROL PANEL1. Switch (OFF, AUTO and MAN positions). 2. Voltagecontrol rheostat. 3. Flash button.Switch (1) is used to make the' selection betweenAUTO, MAN and OFF. In the "AUTO" position thegenerator regulator assembly controls the generatorvoltage. In the “OFF" position the generator voltage willgo to zero. In the "MAN" position generator voltage iscontrolled by voltage control rheostat (2).Flash button (3) is used when the generator voltagedoes not build up. With switch (1) in the "MAN" positionpush flash button (3) until the generator voltage starts tobuild up.NOTICEPress the flash button only until thegenerator voltage starts to build up.If the button is held too long thevoltage will increase to above thecapacity of the generator. This cancause the line circuit breaker to tripor the regulator fuse to open.When flash button (3) is pushed AC current from thegenerator is rectified by a diode on the manual voltagecontrol panel. This rectified (DC) current goes directly tothe generator exciter field. It does not go through controlrectifier CR9.CONTROL ASSEMBLY4. Trigger module. 5. Terminal strip. (4 and5 are not serviced separately - lowestserviceable level is Manual Voltage ControlAssembly)The control assembly is on the back side of themounting bracket for regulator module A1. The controlassembly has terminal strip (5) and trigger module (4).When switch (1) is in the "MAN" position, the action ofelectrical circuits in trigger module (4) control the amountof "on" time for control rectifier CR9.50
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business