TM 10-4130-237-14
5-12.
HIGH PRESSURE SWITCH REPLACEMENT (CONT)
4
5
6
7
To prevent electric shock, make sure power is disconnected from 12/24 VOLT
INPUT FOR STARTING connection before performing this procdure.
Tag three wires from switch. Remove two screws and three wires.
Remove three bracket mounting screws and three flatwashers.
Remove mounting bracket from switch.
Remove high pressure switch and refrigerant line.
b. Installation
1
Install high pressure switch and refrigerant line.
2
Install mounting bracket three mounting screws, and three flatwashers.
3
Connect three wires to switch. Install two screws. Remove tags.
4
Install two screws, two flatwashers, and two wire clamps around ignition wire and refrigerant line.
5-43