TM 10-4130-237-14
5-14. CONDENSER REPLACEMENT (CONT)
3
Remove eight plenum mounting screws and eight flatwashers.
4 Remove eight condenser mounting screws, eight lockwashers, and eight flatwashers.
5
Lift condenser horn skid base.
b. Installation
1
Install new condenser on skid base and aline mounting holes.
2
Install eight condenser mounting screws, eight lockwashers, and eight flatwashers.
3
Install eight plenum mounting screws and
4
Braze copper tube onto elbow fitting.
5
Install discharge tee to condenser fitting.
6
Install pressure relief valve (para 5-15).
flatwashers.
NOTE
If any refrigeration system components have been removed or replaced, in-
stall a new filter-drier before evacuating system (para 519).
5 - 48