TM 10-4130-237-145-16. EXPANSION VALVE REPLAY (CONT)a. Testing1 Locate expansion valve bulb on low pressure line between evaporator and compressor.2 Cut away insulation covering expansion valve bulb being careful not to nick bulb or line.3 Loosen expansion valve bulb hose clamps.4 Loosen screws and carefully slide clamps free of expansion valve bulb.5 Install refrigeration charging manifold and manifold hoses (para 5-9).6 Start engine (para 2-6a) and observe pressure gage on low side of charging manifold.5-51