TM 10-4610-234-13
1.9 LOCATION AND DESCRIPTION OF SYSTEM COMPONENTS-Cont.
2-INCH HOSE CONNECTION KIT (9). Contains 2-inch hose connections for filling tankers, trailers and other
large capacity containers.
HOSE NOZZLE CONNECTION KIT (10). Contains hand-operated nozzles used to dispense water to field
users. Each nozzle connection kit has a quick disconnect connector and a swivel for ease of operation.
BAG FILLER CONNECTION KIT (I 1). Contains hand operated nozzle dispensers used to fill water bags.
ACCESSORY KIT (Not shown). Contains additional hoses, valves, couplings and fittings. Components are
used to adapt the water system to varying site and operational requirements.
WATER TANK CHEST (Not shown). Reusable container stores water tanks and accessories when not in use.
1.10 EQUIPMENT DATA (Refer to Table 1-1).
Table 1-1. Equipment Data
Hypochlorination Unit (Refer to TM 5-4610-233-13&P).
350 GPM Pumping Assembly (Refer to TM 5-4320-226-14).
125 GPM Pumping Assembly (Refer to TM 5-4320-304-14 or TM 10-4320-309-14).
20,000 Gallon Fabric Collapsible Water Tank (Refer to TM 5-5430-226-12).
Water Tank Chest.
Weight (grins) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,200 lb
Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 ft. 8 in.
Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft. 8 in.
Height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000 lb
Section III. TECHNICAL PRINCIPLES OF OPERATION
1.11
GENERAL.
The water distribution system described in this manual is configured for maximum storage and distribution
capacity. Your operating requirements will determine how many of the system components must be con-
nected and in what configuration. Additional components are available in the accessory kit to adapt the sys
tem to varying site and operational needs. Another water system maybe connected to this equipment to in-
crease storage and/or distribution capacity.
Water used in the 40K system is supplied by the Tactical Water Distribution pipeline or other source. Water
drawn into the 40K system by the 125 or 350 GPM pump is supplied to the water storage tanks through 4-inch
collapsible discharge hoses. Control of water flow between the water supply pump and the water tanks is
performed by opening or dosing gate valves on the filler side of the dual tank connection kit. The tanks may
be filled at the same time or filled separately, depending on operating requirements. By filling one 20,000 gal-
lon water tank at a time, the system can discharge water almost immediately after set up.
Potable water is stored in the 20,000 gallon collapsible fabric tanks until needed. When water is required
downstream, gate valves on the discharge side of the dual tank connection kit are opened. Water then flows
from the tank(s) to the suction side of the 350 and 125 GPM discharge pumps. For detailed water tank prin-
ciples of operation, refer to TM 5-5430-226-12.
1-5