TM 10-4610-243-132-10. ASSEMBLY AND PREPARATION FOR USE - cont.n.AssembleBagFilterConnectionKit.Refer to figure 2-21.WARNINGTo prevent contamination of drinking water, make sure protective caps and plugs areinstalled when components are not in use. Do not remove caps and plugs fromcomponents until couplings are ready to be connected.NOTEInstall all gate valves with hand wheel in upright position and valve fully closed.(1)Connect 4 inch x 20 foot discharge hose (2) to tee (1) (from hose nozzle connection kit no. 4).(2)Connect 4 inch x 20 foot discharge hose (3) to 4 inch x 20 foot discharge hose (2).(3)Connect tee (5) to 4 inch x 20 foot discharge hose (3).(4)Connect adapter (4 inch female x 2 inch male (6) to tee (5).(5)Connect 2 inch x 20 foot discharge hose (7) to adapter (6).(6)Connect wye (8) to 2 inch x 20 foot discharge hose (7).(7)Connect 2 inch x 20 foot discharge hose (9) to wye (8).NOTEThe 2 inch gate valves used in this connection kit have a 2 inch female coupling on oneend and a 1-½ inch male coupling on the other.(8)Connect 2 inch gate valve (10) to 2 inch x 20 foot discharge hose (9).(9)Connect 1-½ inch x 25 foot discharge hose (11) to 2 inch gate valve (10).(10)Connect 2 inch x 20 foot discharge hose (12) to wye (8).(11)Connect wye (13) to 2 inch x 20 foot discharge hose (12).(12)Connect 2 inch gate valve (14) to wye (13).(13)Connect 1-½ inch x 25 foot discharge hose (15) to 2 inch gate valve (14).(14)Connect 2 inch gate valve (16) to wye (13).(15)Connect 1-½ inch x 25 foot discharge hose (17) to 2 inch gate valve (16).(16)Install cap (4) on unused male coupling on tee (5).2-56