TM 10-4610-237-12
2.7
ASSEMBLY AND PREPARATION FOR USE - Continued.
f.
Assemble 125 GPM Pump Assembly Connection Kit (Refer to Figure 2-6).
WARNING
To prevent contamination of drinking water, make sure protective caps and plugs are installed
when components are not in use. Do not remove caps and plugs from components until
couplings are ready to be connected.
NOTES
·
Install all gate valves with hand wheel in upright position and valve fully closed.
·
Suction hoses are noncollapsible and discharge hoses are collapsible.
·
With the exception of two adapters, all couplings in this kit are 2-inch diameter.
(1)
Connect reducer (4inch female x 2-inch male) (2) to tee and dual gate valve assembly (1) from single
tank connection kit.
(2)
Connect 20-foot suction hose (3) to reducer (2).
(3)
Connect 2-inch gate valve (4) to 20-foot suction hose (3).
(4)
Connect 20-foot suction hose (5) to 2-inch gate valve (4).
(5)
Assemble and prepare 125 gpm pump (6) for use. Refer to the applicable TM.
(6)
Position 125 gpm pump (6) in water system.
(7)
Connect end of 20-foot suction hose (5) to female (suction) coupling (7) on pump (6).
(8)
Connect 20-foot discharge hose (9) to male (discharge) coupling (8) on 125 gpm pump (6).
(9)
Connect check valve (10) to 20-foot discharge hose (9).
(10) Connect 2-inch gate valve (11) to check valve (10).
(11) Connect 20-foot discharge hose (12) to 2-inch gate valve (11).
(12)
Connect reducer (4-inch male x 2-inch female) (13) to tee and dual gate valve assembly (14) from
single tank connection kit.
(13) Connect end of 20 foot discharge hose (12) to reducer (13).
2-20