TM 10-4610-237-12
2.7
ASSEMBLY AND PREPARATION FOR USE - Continued.
g.
Assemble 2-Inch Hose Connection Kit. (Refer to Figure 2-7).
WARNING
To prevent contamination of drinking water, make sure protective caps and plugs are installed
when components are not in use. Do not remove caps and plugs from components until
couplings are ready to be connected.
NOTE
·
Install gate valve with hand wheel in upright position and valve fully closed.
(1)
Connect 4-inch x 20*foot discharge hose (1) to male (outlet) coupling on hypochlorination unit (8).
(2)
Connect 4-inch x 20-foot discharge hose (2) to 4-inch x 20foot discharge hose (1).
(3)
Connect tee (3) to 4-inch x 20-foot discharge hose (2).
(4)
Connect reducer (4-inch female x 2-inch male) (4) to tee (3).
(5)
Connect 2-inch gate valve (5) to reducer (4).
(6)
Connect 2-inch x 20-foot discharge hose (6) to 2-inch gate valve (5).
(7)
Unfold nozzle stand assembly (7) and attach discharge hose (6) to bracket on stand.
2-22