TM 10-4610-237-12
2.7
ASSEMBLY AND PREPARATION FOR USE - Continued.
NOTES
·
Install all tee and gate valve assemblies with hand wheels in upright position and valves fully
closed.
·
Reposition connection kit components as needed to prevent kinks or tight bends in hoses.
·
Suction hoses are noncollapsible and discharge hoses are collapsible. All couplings in this kit are
4-inch diameter.
(1)
Connect 20foot suction hose (1) to male discharge elbow (2) on water tank (11).
(2)
Connect suction hose (1) to tee and dual gate valve assembly (3) that has two female and one male
coupling.
(3)
Connect male end of 10-foot suction hose (4) to tee and dual gate valve assembly (3).
(4)
Connect suction hose (4) to water source.
(5)
Connect 20-foot discharge hose (5) to female filler elbow (6) on water tank ( 1).
(6)
Connect 20-foot discharge hoses (7 and 8) to discharge hose (5).
(7)
Connect discharge hose (8) to tee and dual gate valve assembly (9) that has two male and one female
coupling.
(8)
Connect I0foot discharge hose (10) to remaining male coupling on tee and dual gate valve assembly
(9).
(9)
Connect discharge hose (10) to female (inlet) coupling on hypochlorination unit (12).
2-18