Parallel Operation3. After the engine has run long enough to warm up,bring it up to synchronous speed (the same frequency asthe unit on the line). The synchronizing lights will beginto blink.4. Using the governor control adjust the speed until thelights blink very slowly.5. The lights are off when the voltages of the two unitsare in phase. At this point very quickly close the breakerwhile the lights are out.6. Use governor controls to share KW load betweenengines7. After generator temperature has stabilized (1 hr.),adjust the droop control of each generator so as to sharethe reactive load and to limit the circulating currents.Less droop (moving control CCW) increases the reactivecurrent carried by the generator.The frequency of the incoming unit should be slightlygreater than the line frequency. This will allow theincoming unit to assume some of the load rather thanadd to the system load.Load Division--(Speed Droop)Once two units have been paralleled their share of theload is determined by the governor control setting. If twounits of the same capacity and the same governorcharacteristics have the same governor control settingsthey will share the load equally.To transfer the load from one engine to the other followthis procedure:The total load must not exceed the capacity of theengine.1. Increase the governor speed control of one unit toincrease the load.2. Reduce the governor speed control of the other unitto decrease the load on that unit.3. Raise or lower the governor speed control of bothunits to change system frequency.Circulating CurrentsWhen two units are paralleled there will be circulatingcurrents. These currents are not doing useful work, butare flowing between the generators. By determining thetotal generator amperage and subtracting the amperagegoing to the load, the amount of circulating current canbe determined.Circulating currents are caused by voltage differencesbetween the two units.With cold generator sets, circulating current may be ashigh as 25% of rated amperes, without being consideredharmful. Circulating current is part of the total generatorcurrent and this total must not exceed the amperagerating.As the generators warm, the circulating currents willdecrease. The ammeter readings should decreaseslightly, but the voltage meter readings should remainconstant.16
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business