Voltage AdjustmentThe voltage level and voltage droop adjustmentsdetermine the amount of circulating currents betweengenerators. Carefully matched voltage regulatoradjustments will reduce the circulating currents. Loadsof .8 power factor (primarily motors) require a generatorvoltage droop of about 5%. Voltage droop is expressedas the percentage of voltage change from no load to fullload. Use the same voltmeter to make adjustments oneach unit to be paralleled.1. Adjust voltage as described for Single Unit Operation,Initial Start-Up.2. With the engine running at high idle, turn the voltagedroop clockwise about 1/2 of full range. If driven load isto be unity power factor, set the voltage droop control onall generators at 1/2 of full range and proceed to Step 7.If driven load is to be normal (0.8 power factor) proceedto Step 3.3. Readjust the voltage level control until the voltage isabout 5% above desired voltage.4. Apply full load at .8 power factor.NOTE: If a generator is to be paralleled with othergenerators, the voltage droop of each generatormust be the same to satisfactorily divide reactiveload.5. Readjust the voltage droop control to obtain desiredvoltage with full load at .8 power factor.6. Repeat Steps 3, 4 and 5 for each generator to beparalleled until line voltage is equal to desired level at .8power factor and no load voltage is approximately 5%above rated voltage.7. Parallel generators and apply the driven load (see thetopic Operation/Paralleling). If the sum of the amps ofthe individual generator amperes exceeds the total ampsgoing to the load by 10% at full load, adjust voltagedroop controls to share current proportionally betweengenerators.CAUTIONDo NOT exceed rated ampere load onany single generator.8. Tighten the locknuts on all controls and install theaccess cover. Condition 3 has been met.Starting Multiple UnitsStarting-Units are started the same as single units.ParallelingUnits may be paralleled at no load or paralleled withunits under load. To parallel two or more units thefollowing conditions must be met:1. Same phase rotation.2. Same voltage level.3. Same voltage droop.4. Same frequency.5. Voltages must be in phase.The first three conditions have been met in the initialstart-up for parallel operation.1. Start the unit to be paralleled according to theprocedure in the engine operation section.2. Turn the synchronizer lights on.15
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business