Generator Set Control Panel (If Equipped)
Shutting Down
A timer in the transfer switch allows transfer of the load
to another source and the cool down timer in the control
panel allows the engine to continue running for up to 2
minutes before stopping.
Starting the Engine After a Shutdown Caused by Engine Failure
1. Turn engine control switch to STOP position.
2. Find cause of shutdown and correct it.
3. Turn control switch to OFF/RESET position.
4. Operate the engine with the engine control switch in
MANUAL. Make tests as necessary to make sure the
condition that caused the shutdown has been corrected.
Oilfield Generator
For SCR Controlled Electric Rigs
Oilfield generators are now available for use with SCR
controlled electric oil rigs, that do not use a voltage
regulator. The function of the generator control is
performed by the drilling electrical control system.
Consult the drill rig builder on questions pertaining to
generator
control
(voltage
regulation,
paralleling,
loadsharing, etc.).