SPECIAL APPLICATION SWICHGAGES": ABS, EO, DP, VWC, ST
ALARM BEFORE SHUT-DOWN
TWO SWITCH OPTION
ABS: SWICHGAGEâ with Alarm Before Shut-down
The ABS has a standard, front limit-contact for low pressure
equipment shut-down and an internal, SPDT micro switch for
Alarm Before Shut-Down (see Wiring Diagram). When the low
side of the micro switch SETS (preset point, on falling
pressure), the NC side of the switch completes a circuit to
activate an alarm. From this point the pressure must increase
approximately 10% of scale before the micro switch will
RESET and open the circuit; if pressure falls, the shut-down
circuit will be completed.
NOTE: The front contact shut-down limit
setting (adjustable) and micro switch low
point are preset at the factory; if settings
other than standard are necessary, then
specify when ordering.
FILTER DIFFERENTIAL PRESSURE
DP: Differential Pressure SWICHGAGE
Installation: 1) connect the input side of the filter to the center
port: 2) connect the filter output pressure to the upper port -
CAUTION: use a 7/16" wrench on the
upper port's wrench flats to prevent
damage to the gauge. DO NOT over
tighten port connections; 3) set the limit
contact
to
the
manufacturer's
filter
specifications: 4) connect wiring to alarm
and/or shutdown devices.
DRY AIR CLEANER RESTRICTION
VWC: Water Column Calibrated, Vacuum SWICHGAGE
Installation: 1) mount the VWC away from engine vibration; 2)
run the vacuum line from the gauge to a point between the air
cleaner and (a) carburetor on carbureted engine, (b)
turbocharger on turbocharged diesels, (c) the engine on
naturally aspirated diesels. NOTE: a flexible section is
essential at some point in the vacuum line to eliminate
vibration. Be sure the SWICHGAGE is grounded in a 12 or
24 volt system, and that the alarm used Is of the same voltage
as the battery.
MICRO-SWITCH! LIMIT CONTROL
EO: SNAP-ACTION Pressure SWICHGAGE
An EO is the combination of a MURPHYGAGEâ and a SPDT micro
switch. The switch will SET (see wiring Diagram) at its preset low
pressure point on falling pressure. As the pressure rises, the switch
will RESET, approximately 10% of scale above the low pressure
SET point. (The 10% difference is inherent in the physical
movement of the micro switch.) By knowing the low pressure SET
point, this 3 wire SWICHGAGE can be used to make or break a
circuit.
For Example, you have a 0-100 psi EO with a SET point of 15 psi:
the switch will RESET at +10% of scale or 25 psi. This EO could be
wired to light a lamp on low pressure start-up, and then put out the
lamp as pressure rises past 25 psi.
The SPDT micro switch is rated 3 A @ 30 VDC inductive and 4 A @
125 VAC inductive.
FLASHING LED ALARM
ST: LED Flashes On SWICHGAGE''
Closure The ST has a standard, front limit-contact for low pressure
alarm. For shut-down or auxiliary alarm, wire to compatible rating,
see examples of Murphy audible alarm and magnetic switches given
below.
TROUBLE SHOOTING TIPS (Where problem appears to involve Murphy products)
PROBLEM
PROBABLE CAUSE & POSSIBLE CORRECTION
Engine will not start
Blown fuse in magnetic switch circuit: replace with 14 A fuse.
False ground in control circuit: repair.
Open circuit (Fault Sensitive): repair.
Control circuit overloaded by accessories: reroute accessories.
False Shut-down
Intermittent shorting in wiring due to wear or insulation breakdown
check all wiring, replace as necessary.
Fault Sensitive circuit has intermittent open or short: check all
wiring, replace as needed.
Vibration causes the magnetic switch to trip: repair, replace or
relocate switch as needed.
SWICHGAGE closes but does not trip
Incomplete circuit: locate open circuit and repair.
the magnetic switch or kill the engine.
Magneto not providing power to primary terminal post: repair magneto.
C.D. type magnetic switch being used with magneto or battery:
replace with correct switch.
SWICHGAGE closes and kills engine.
Defective magnetic switch binds outside, prevents trip: adjust or
but does not trip the magnetic switch
replace the switch.
Conventional magnetic switch is used with C.D. ignition: replace
with a C.D. designated switch.
TATTLETALE tripped but engine
Lost ground to kill engine: repair.
still running (mag. or C.D.).
Clogged lines or pulsation dampener: remove and clean or
Pointer will not operate properly.
replace.
inaccurate readings.
Kinked/crimped/broken pressure or vacuum line: replace line.
Pointer or contact burned in two
Without exception this Is caused by incorrect wiring or a short
circuit: refer to wiring diagrams and recheck wiring:
replace SWICHGAGE'.
If you need additional assistance, contact YOUR LOCAL MURPHY DEALER, or a Murphy representative at one of the
offices listed on this form.