TM 5-3820-256-10
(b)
Make connections to 120/240 vac terminal strip. See Figure 2-33.
(c)
Remove the right side panel from the welder/generator.
(d)
Insert leads through strain relief on the generator rear panel. Take leads over to terminal strip. See
Figure 2-33.
(e)
To obtain 120 vac auxiliary power, see Figure 2-33 and proceed as follows:
1
Connect one lead to terminal A or B on terminal strip IT.
2
Connect remaining lead to terminal C or D on terminal strip 1T.
3
Make sure that the jumper links on terminal strip iT are positioned for 120 vac.
4
Connect the ground lead to ground terminal below terminal strip IT.
5
Tighten strain relief on the generator rear panel.
6
Install right side welder/generator panel and resume operation.
(f)
To obtain 240 vac auxiliary power, see Figure 2-33 and proceed as follows:
1
Remove and retain jumper links from terminal strip iT.
2
Move lead no. 58 to terminal D on same side of terminal strip IT.
3
Position jumper links on terminal strip iT for 240 vac.
4
Connect line leads to terminals A and D on terminal strip 1T.
5
Connect ground lead to ground terminal below terminal strip 1 T.
6
Tighten strain relief on the generator rear panel.
7
Install right side welder/generator panel and resume operation.
(g)
To obtain 120/240 vac auxiliary power, see Figure 2-33 and proceed as follows:
1
Remove and retain jumper links from terminal strip iT.
2
Move lead no. 58 to terminal D on same side of terminal strip 1T.
3
Position jumper links on terminal strip IT for 240 vac.
4
Connect line leads to terminals A and D on terminal strip 1T.
2-67