INSTALLATION
GENERAL
The assembled Kidde Hose applications are shown on the installation drawings included in this book; these drawings
should be consulted for identification of parts.
This equipment should be installed where the hose and discharge horn are easily accessible to all fire hazards, such as
fuel pumps, electrical apparatus, etc.
Mount the cylinder (s) vertically. For local control systems, the control head should be in a position where it may be easily
operated.
In the case of remote control system, the break-glass pull box is to be mounted along side
the hose reel or rack.
The following procedure has been found by experience to be the most efficient and practical method of installation. It is,
therefore, recommended that the installation be made in accordance with these instructions.
Refer to drawings No. for specifications of the pipe and fittings to be used for conducting
carbon dioxide.
DETAILED INSTRUCTIONS
1.
Fasten the cylinder strap anchors securely to the bulkhead in accordance with dimensions as shown on the
installation drawing, measuring from the bottom of the cylinders. When necessary, allow for a chock to be placed
under the cylinders to prevent corrosion.
2.
Set the cylinder (s) in place, leaving the shipping caps on during this operation. Place the cylinder straps in position
and bolt handtight to the bulkhead.
3.
Remove the shipping cap from cylinders. Turn cylinder (s) so that the safety outlet is facing the bulkhead, then
tighten cylinder strap bolts securely. Remove top and side protecting caps from cylinder valves.
4.
Mount the hose rack or reel as shown on installation drawing L-79200 or L-79013.
5.
For remote control systems only, install the break-glass pull box adjacent to the reel or rack. The control cable
should be enclosed in pipe or conduit. This should be standard 3/8" size of hot dipped galvanized steel or standard
weight brass. Run control cable piping as directly as possible to cylinders. BENDS OR OFFSETS ARE NOT
PERMITTED. Kidde corner pulleys are to be used at all angle bends. Fasten cable to remote control head as
shown on Drawing L-82134.
6.
Provide for the connection of cylinder (s) to the distributing hose. For details, refer to the installation drawing
included in this book. In making connections, pipe dope or red lead should not be used, but tighten all connections
securely with a wrench.