ELECTRICAL VOLTAGES AVAILABLE
TESTING AND ADJUSTING
SR 4 Generators directly meet these requirements.
Single-phase loads should be distributed equally from
the three lines to the neutral giving 230 volts single-
phase (at 400 volts, three-phase). Industrial 50 Hz
three-phase loads in the range of 480 volts can be
directly supplied by the 480 volt 50 Hz generators.
However, if single-phase voltage in the range of 220
volts is also required from a 480 volt three-phase
system, single-phase step down transformers will be
required.
Larger 60 Hz industrial loads are generally three-phase
in the range of 460 to 480 volts. Single-phase 120 volt,
120-240 volt or 240 volt loads are almost always
supplied from transformer banks, operating from the 460
to 480 volt three-phase service. The 480 volt 60 Hz SR
4 Generators match this requirement directly. With the
stator coils parallel connected, this range of generators
will directly match large industrial three-phase, 230-240
volt loads.
Other 60 Hz commercial service supplies power in the
range of 120/208Y to 125/216Y volts in a 4-wire "Y"
connected
single-phase/three-phase
system.
The
nominal 120/208Y 60 Hz generator is directly applicable.
Motor starting ability compares to the nominal 240 volt
generator operating at 240 volts. The broad voltage
range 5N43, 5N46, 5N48, 5N56, and 5N58 Generators
connected for low voltage will also directly meet these
application, as the voltage level control has adequate
range.
When these broad range generators are operated in the
208-416 volt range, motor starting ability is good, but of
course, less than when operating at the 240-480 volt
range. The expected voltage dip at the 208-416 setting
will approximate 35% when starting 0.5 hp of motor per
kW of generator prime power rating.
Another common 60 Hz commercial power service
distribution comes from Delta connected transformers,
which will simultaneously supply 240 and 120 volt single-
phase. Such systems can be quite satisfactorily
supplied from the 60 Hz, 120/208Y volt SR 4 Generator,
since connected equipment readily accepts a ±10%
voltage tolerance. When the prospective installation
demands voltages exactly equal to the original,
transformers will be necessary, as 120 and 240 volts can
not be obtained simultaneously from a "Y" connected
generator.
In any installation, single-phase loads should be
distributed as equally as possible around the three-
phases to avoid generator derating or excessive heating.
Single-phase
loads, balanced within 10%, are considered acceptable
within present engineering practices. In any combination
of single-and three-phase loads, individual line current
should not exceed the generator nameplate ampere
rating.
Voltage Modifications
There are areas where existing commercial 50 Hz power
systems will eventually be converted to 60 Hz. These
areas require a generator which will presently produce a
given voltage at 50 Hz and later be capable of producing
the same voltage at 60 Hz. Suitable generator
application depends on present voltage.
If the present required 50 Hz three-phase voltage is 240
or 480, and the future system will be 60 Hz, 240 or 480
volts, the 50 Hz 240-480 volt generator is suggested.
This generator will produce 300-600 volts at 60 Hz.
However, the exciter-regulator system can easily be
reconnected to lower generated voltage to 240-480 at 60
Hz when the change in commercial frequency occurs.
As originally constructed, this 50 Hz, 240-480 volt
generator has the voltage regulator and exciter field
tapped into the three generator coils forming the center
"Y". These coil taps terminate at terminals 20, 22, and
24 of the regulator terminal board. Remove the wires
from the terminal board, and carefully insulate each wire
to avoid any possible connection or ground. Install new
No. 14 gauge, 600 volt insulated flexible wires from the
terminal board to the generator line leads as follows:
From Terminal Board
To Line Lead
No. 20
T-9
No. 22
T-7
No. 24
T-8
The generator will now produce 240 or 480 volts at 60
Hz. The modified generator has the same kVA rating at
60 Hz as it did originally at 50 Hz. Parallel operation is
not affected. Since the modified excitation system is
running at a reduced excitation level, the ability to start
very large motors will be reduced. The range of voltage
level control is also slightly reduced.
If the application presently requires three-phase 50 Hz
voltage at 400 volts, and the future 60 Hz three-phase
voltage will also be 400 volts, the 200-400 volt 50 Hz
generator is a good choice. Without modification, this
generator would produce 240 or 480 volts at 60 Hz. A
special connection of the
96