REMOTE VOLTAGE CONTROL
TESTING AND ADJUSTING
SUBJECT:
Remote Voltage Level Control For Caterpillar Generators
BUSINESS:
Building Services, Material Handling, Marine, Petroleum, Agriculture
PRODUCT/APPLICATION:
Generator Sets, SRCR and SR 4
It is sometimes desirable to control the voltage level of a
generator at a remote-mounted control panel rather than
at the generator. These instructions cover the selection
and installation of a remote potentiometer to provide the
same full range of voltage level control as the original
generator mounted control. These instructions move the
point of control from the generator to the remote
location.
Selection of Potentiometer Control
If screw driver slot adjustment with locking feature is
acceptable, the original generator mounted control can
be moved to the remote location. A parts service control
(duplicate of original) could also be used. If a knob
adjustment and indicator dial is desired, select a 25 watt
wire wound potentiometer of suitable shaft length to
accommodate the knob and dial. SRCR Generators
require a 25 ohm, 25 watt potentiometer. SR4
generators require a 500 ohm, 25 watt potentiometer.
Wiring the Remote Voltage Level Control:
1.
Prepare three lengths of No. 14 600 volt
insulated wire. Use one yellow wire, one red
wire, and one white wire. Cable these wires to
avoid damage. Connect the potentiometer to
the three wires as follows:
Yellow Wire - Solder to the clockwise end of the
potentiometer.
Red Wire - Solder to the counter-clockwise end
of the potentiometer.
White Wire - Solder to the sliding arm contact of
the potentiometer and to the counterclockwise
end of the potentiometer along with the red wire.
2.
Disconnect the existing generator mounted
voltage level control at the terminals noted
below. Insulate each of the removed wires and
secure these to avoid any vibration damage.
Connect the wires to the terminals designated:
A.
SRCR Generators With Panel Mounted
Two Phase Half Wave Exciter (Serial
Numbers below 1500)
1.
Remove
existing
white
wire
at
terminal 17, red wire at terminal 20,
and yellow wire at terminal 16.
2.
Connect new white wire to terminal
17, red wire to terminal 20, and
yellow wire to terminal 16.
B.
SRCR Generators With Tray Mounted
Two-Phase Half Wave Exciter (Serial
Numbers 1500-2000)
1.
Remove existing white wire from
terminal
TB1-3,
red
wire
from
terminal TB1-5, and yellow wire
from terminal TB1-4.
2.
Connect new white wire to terminal
TB1-3, red wire to terminal TB1-5,
and yellow wire to terminal TB1-4.
C.
SRCR Generators With Tray Mounted
Two-Phase Half Wave Exciter (Serial
Numbers above 2000)
100