ELECTRICAL VOLTAGES AVAILABLE
TESTING AND ADJUSTING
line leads, called "Zig-Zag" will lower the nominal 60 Hz
voltage about 13%, making it usable as a 400 volt unit.
Voltage level adjustment range remains about +5%.
With a zig-zag connection, the excitation level at 60 Hz,
400 volts is essentially the same as it was at 50 Hz, 400
volts. The zig-zag connected generator therefore will
retain its excellent motor starting ability. The final
connections are shown in Figure 6.
Connect T1 to T8
T2 to T9
T3 to T7
Line Leads are T4, T5, T6
Neutral is TO
If the zig-zag connected generators are to be operated in
parallel or with other generator sets, additional line leads
must be run through the window of the droop
transformer (3N1964). This is necessary to retain the
correct droop transformer voltage relationship when a
zig-zag connected generator is paralleled.
Observe the direction and the number of T-8 line leads
coming out of the generator and passing through the
transformer window. Also observe the number of times
the T-8 lead (or leads) pass through the transformer
window. An equal number of T-2 leads, must pass
through the window the same number of times, and in
the same direction as the existing T8 leads. The end of
T2 is then connected to T9 as shown in Figure 6.
On some generators the droop transformer will not
accommodate the additional line leads through the
window. Instructions for the necessary conversion are
shown in Figures 7 and 8.
Correctly connected zig-zig generators will operate in
parallel. In single or parallel operation, the 50 Hz kVA
ratings would generally apply to a zig-zag connected
generator operating at 60 Hz.
Zig-zag connections (with proper droop transformer
modification if parallel operation is expected) may also
be applied to a 480 volt 50 Hz generator to cause it to
produce 420 volts at 50 Hz. The original line ampere
rating of a 480 volt 50 Hz generator would apply to the
unit when operated at 420 volts. kVA capacity is
reduced 13%. Modified units will operate in parallel.
There are other areas of the world where 60 Hz
generator sets are now used as prime power, but these
may eventually be required
to serve in a standby system when commercial 50 Hz
power
becomes
available,
or
is
required
by
governmental decree. In these instances the oncoming
or future power system will probably be one of the above
listed common 50 Hz three-phase voltages (i.e., 380,
400, or 415). As noted previously, a 60 Hz 480 volt
generator will produce 400 volts at 50 Hz. Normal
voltage level adjustment range of the SR 4 Generator is
adequate to meet the lower and upper limits of the
probable future voltages.
Figure 6
Zig-zag connection to obtain 420 volts from a 480 volt
generator or 87% of normal volt from any SR 4
Generator. For parallel operation, the droop transformer
must enclose 1-leads as shown. Note the direction of T2
through transformer and the connection to See Figure 7
for detail when droop transform will not accommodate
additional line leads.
The following generators require installation of a second
3N1964 Droop Transformer to provide space for
additional line leads necessary for operation of zig-zag
connects SR 4 Generators in a parallel system.
5N2
5N24
5N36
5N146
5N6
5N5
5N28
5N37
5N57
5N6
5N6
5N29
5N39
5N58
5N13
5N33
5N40
5N59
5N23
5N34
5N42
5N61
97