REMOTE VOLTAGE CONTROL
1.
Remove existing white wire from terminal
TB1-3, red wire from terminal TB1-5, and
yellow wire from terminal TB1-4.
2.
Connect new white wire to terminal TB1-3,
red wire to terminal TB1-5, and yellow
wire to terminal TB1-4.
D.
SRCR Generators With Panel Mounted Single-
Phase Full Wave Exciter (Serial Numbers below
1500)
1.
Remove existing white wire from terminal
TB2-4, red wire from terminal TB2-5, and
yellow wire from terminal TB2-3.
2.
Connect new white wire to terminal TB2-4,
red wire to terminal TB2-5, and yellow
wire to terminal TB2-3.
E.
SRCR Generators With Tray Mounted Single-
Phase Full Wave Exciter (Serial Numbers 1500-
1999)
1.
Remove existing white wire from terminal
TB1-3, red wire from terminal 10 on noise
filter (FL1), and yellow wire from terminal
TB1-4.
2.
Connect new white wire to terminal TB1-3,
red wire to terminal 10 on noise filter
(FL1), and yellow wire to terminal TB1-4.
F.
SRCR Generators With Tray Mounted Single-
Phase Full Wave Exciter (Serial Numbers above
2000)
1.
Remove existing white wire from terminal
TB1-3, red wire from terminal TB2-5, and
yellow wire from terminal TB1-4.
2.
Connect new white wire to terminal TB1-3,
red wire to terminal TB2-5, and yellow
wire to terminal TB1-4.
TESTING AND ADJUSTING
G.
SR 4 Generators (Single Phase Half Wave
Excitation and Regulation)
1.
From terminal 7, remove yellow wire that
extends to the clockwise end of voltage
level control.
2.
Connect new yellow wire to terminal 7,
new red wire to terminal 6.
101