CIRCULATING CURRENTSTESTING AND ADJUSTINGOperating conditions as just described are not alwayspossible over the entire load range of the generators.Electrical and mechanical variations in generators causea small difference in ampere or kVA division. Neither isexactly proportionate to kW load division. The differenceshows up in the panel ammeter indications: the sum ofindividual generator line currents exceeds the loadcurrent.Acceptable levels of circulating current result if thepublished procedures are followed for voltage level,regulator gain, and voltage droop on SRCR and SR 4generators. These adjustments are always made withthe generator at or near operating temperature. When a"cold" unit is paralleled to the bus, circulating currentsmay be noted. However, these will decrease as theincoming generator reaches its operating temperature.These currents are seldom cause for concern. Whereexcessive circulating currents do exist, the cause isgenerally found to be error in the adjustment procedureor in operating procedure.When different sizes of generators are used, or wheredifferent types of voltage regulators are used, the bestadjustment results from using the actual plant load.Voltage droop levels should be established from areference voltage level, and at a reference frequency.It is generally desirable to have the same voltage droopon all generators. This means that each generatorshould reduce its voltage an equal amount (3% to 5%X)between no-load and expected full load. Where differentsize generators are involved, it may be impractical tomake the full load droop adjustment on the largergenerators. A close approximation can be made byconsidering the droop system as a linear device. Selecta plant load equal to at least three-fourths of the smallergenerator capacity. Set the required droop on thissmaller unit (example 5%). Transfer-parallel this sameload to the larger generator and establish the referencefrequency. Set the droop proportionate to the capacity.Example: 5% was set on the smaller unit with full load.That load is one-half the larger generator capacity. Setthe droop on the larger generator at 2.5%. The resultingadjustment will be quite adequate.Operating errors can cause very high circulatingcurrents. These generally occur where indicatinginstruments are limited to voltmeters and ammeters. It isentirely possible to have one generator set absorbingpower from the system, and have the ammeters showing"correct" currents. To avoid this, the operator shouldalways have the incoming generator set running slightlyfast, as shown by synchronizing light brilliance at 6 to 10times per minute prior to closing the circuit breaker. Thiswill assure that the incoming generator supplies power(kW) to the load at the time of breaker closure. Load isthen added to the incoming generator set by increasingthe setting of its governor control, or decreasing thesetting of the on-line generator set governor controls.Operating refinements to regulator adjustment are easilymade on installations equipped with VAR meters, powerfactor meters, or wattmeters and line ammeters. (If thesystem includes only ammeters, regulator adjustmentsmust be made with a single unit on the line.) Wherepower factor or VAR meters show equal indications,each generator is supplying its share of the load currentreactive amperes, and circulating current betweengenerators is at a minimum. Example: load power factoris 0.8. Generator No. 1 indicates 0.7 P.F. GeneratorNo. 2 indicates 0.85 P.F. These meter readings tell theoperator that Generator No. 1 is supplying too muchmagnetizing current to the load, and possibly toGenerator No. 2. The magnetizing current of GeneratorNo. 1 can be reduced simply by lowering its voltagelevel. Or, if desired, by raising the voltage level ofGenerator No. 2, the operating power factors can beequalized. Circulating current is then at a minimum.Wattmeters and ammeters can provide the informationnecessary to accomplish operating or on-line voltagelevel adjustments.Example:Load kW 500, Load Line Amperes 750,Voltage 480Generator No. 1, Load kW 250,Line Amperes 350Generator No. 2, Load kW 250,Line Amperes 450These meter readings indicate that Generator No. 2 issupplying more than its share of magnetizing current.This is true because Generator No. 1 is operating at apower factor of 0.86 which is higher than the load powerfactor of 0.80, and generator No. 2 is operating at apower factor of 0.67 which is lower than the load powerfactor. Decreasing the voltage level setting of GeneratorNo. 2 will reduce its magnetizing current and increasethe power factor. At the same time the magnetizingcurrent from Generator No. 1 will increase, and itspower factor will decrease.When loads are not equal, the calculated power factor ofeach generator can be used124
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business