GROUNDING
TESTING AND ADJUSTING
SUBJECT:
Grounding SRCR and SR 4 Generators
BUSINESS:
Building Services, Marine, Material Handling
PRODUCT/APPLICATION:
Generator Sets
1. In any generator set installation, the frame of the
generator must be positively connected to an earth
ground or to the hull of a vessel. This connection is
the first one made at installation, and the last one to
be removed. If the generator set is on flexible or
resilient pads, the ground connection must be
flexible to avoid possible breakage in later operation.
Ground connection cable or straps should have at
least the current carrying capacity of the largest line
lead to the connected load. Joints in cables or
straps must be clean, free of electrical resistance,
and protected from possible oxidation. Bolted
ground connection joints eventually oxidize, and are
frequent sources of radio frequency interference.
Silver soldered, bolted joints are electrically and
mechanically sound.
a.
The radio frequency noise suppressor in early
SRCR
generators
(below
S/N
2000)
is
connected to the generator frame. Inadequate
frame grounding can result in interference to
communication
or
audio
equipment
and
improper operation of electronic governors.
b.
Where local codes permit, an effective ground
connection can be made to an underground all
metallic water piping system. The growing use
of plastic and cement type water pipes makes
water pipe connections hazardous as well as
ineffective. One or more approved corrosion
resistant ground rods, driven at least ten feet
(three meters) into damp soil, are effective. In
dry, sandy soil an extensive wire ground mat
may be required.
2. "Y"-connected generators should have the neutral
(and frame) grounded when the generator is
installed unless definite measures are taken to
prevent grounds on the load side. (NOTE:
Noncurrent 2400-Volt generators are manufactured
with the neutral wire connected to the generator
frame.)
a.
If the neutral wire is not grounded and one of the
load phase leads becomes grounded, the
resulting voltage surge may damage the noise
suppressor on SRCR Generators with serial
numbers below 2000.
b.
If the neutral wire is grounded and one of the
phase leads becomes grounded, the excessive
current will open the load circuit breaker or
collapse the generator voltage. The result
depends on the particular generator electrical
characteristics, type of fault, and circuit breaker
trip rating. An under voltage device may be
required to provide adequate short circuit
protection.
c.
There are some instances in which it is
undesirable to ground the neutral wire. In these
applications where definite measures (ground
fault protective circuits) have been taken to
prevent grounds to the phase leads, an
ungrounded
generator
neutral
lead
is
acceptable. Ground fault protection requires
that the entire group of distribution circuits be
studied and treated as a system. The owner
should engage a competent consultant if a new
distribution system is being developed, or if an
existing system is to be modified for ground fault
protection.
120