CIRCULATING CURRENTSTESTING AND ADJUSTINGto correctly distribute magnetizing current and keep thecirculating currents to a minimum. Example:Load kW 700, Load Line Amperes 1,100,Voltage 460Generator No. 1, Load kW 250,Line Amperes 500Generator No. 2, Load kW 450,Line Amperes 630It should be obvious that the voltage level setting onGenerator No. 2 is too low. Adjustments could be madeto one or both until No. 1 shows a line ampere readingof about 390, and the line ampere reading of No. 2shows about 700 amperes. At these conditions, bothgenerators will be operating at the same load powerfactor of 0.8. Circulating current is at a minimum.Refinements as described above will assure highlysatisfactory operation of paralleled generator sets.SummaryCirculating currents exist in paralleled generators whenthe several generators are attempting to operate atdifferent voltages although they are connected togetherthrough the common bus. These circulating currentsreduce the effective excitation of one or moregenerators, and increase the effective excitation ofothers. Generator voltage is directly related to exciteroutput. Hence, an attempted generator voltagedifference is the result of different exciter output. Exciteroutput is controlled by the voltage regulator, and ultimatecontrol of circulating current is a function of the regulator.Effect of Circulating CurrentsOnLoadSensingElectronicGovernorsThe Woodward 2301 load sensing governor can react toexcessively large circulating currents. With correctadjustment of generator voltage regulators, the loadsensing governor responds to true power or kW load onthe generator set. However, when the value ofcirculating current between generators approaches thevalue of the actual load current, the governors may reactto these excessive circulating currents and change thekW load division between generator sets. Load transfermay be slow, or it may be rapid. There is no predictablepattern since the observed action depends on thecondition of the generator voltage regulators controllingthe several generators.Incorrectly adjusted voltage regulators are the mostcommon cause of the "load shift" problem. It is generallyfound that initial generator regulator adjustments fail toinclude adequate voltage droop or cross-currentcompensation. This difficulty can also cause operatingerrors.Some commercially available generator control panelsfor use with commercially avail-able generators include aswitch that bypasses the voltage droop circuit in thevoltage regulator. These switches have various namessuch as "Single-Parallel" or "Droop In Droop Out."Operators incorrectly position these switches duringparallel operation, causing one or more generators tooperate without voltage droop or cross-currentcompensation. Circulating currents can greatly increaseunder these conditions. Governors will generally react.Switchboard wiring errors, such as reverse-connectedcurrent transformers (used as part of the droop or cross-current system), can also cause load shift problems. Inthese instances, the voltage droop system causes a risein generated voltage as the line current increases.Circulating currents can increase rapidly, and possiblycause circuit breakers to open. Governor reaction maybe noted just prior to circuit breaker opening.125
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business