Generator Bearing (Inside Bearing Type RFA)
Disassembly and Assembly
6. Cut the plastic ties which hold the two wires (F1 and
F2) (6) that go to the regulator from the core assembly
(exciter field).
7. Disconnect the two wires (F1 and F2) (7) from the
regulator terminal strip.
8. Remove two nuts and bolts (8) that help hold the core
assembly to the bracket.
9. Remove two bolts (9) and the core assembly from the
bracket.
10. Put cardboard between the rotor assembly and the
stator assembly This will keep the rotor off the stator
when the bracket is removed.
11. Support the frame assemblies (11).
12. Remove six bolts and the bottom cover (12) from
the brackets (10).
13. Remove four bolts and two retainers that keep the
bearing in position.
133