TM 10-4320-303-132.3.5 BoostPumpingStationAssembly .(Continued)Figure 2-19. Boost Pumping Station and Discharge Components Assembly.f. Remove plastic cap from discharge port (Figure 2-19, 1) on 600 GPM pumping assembly, referenceapplicable technical manual for discharge port location on 600 GPM pumping assemblies not shown.If plastic cap has not been removed, remove it and retain cap for movement or storage.CAUTIONTo prevent damage to pump, make sure arrow on check valve points away frompump.g. Install 6 inch check valve (3) on pump discharge port (1) with grooved-end pipe quick disconnectcoupling clamp (2) (para 2.3.3.2). Ensure 6 inch check valve (3) is installed with arrow pointing awayfrom 600 gpm pumping assembly discharge port (1).h. Install 6 inch x 20 foot hose assembly (5) on end of 6 inch check valve (3) with grooved-end pipequick disconnect coupling clamp (4) (para 2.3.3.2).i. Install 6 inch butterfly valve (7) on end of 6 inch x 20 foot hose assembly (5) with grooved-end pipequick disconnect coupling clamp (6) (para 2.3.3.2).j. Install 6 inch lateral grooved pipe fitting (9) on end of 6 inch butterfly valve (7) with grooved-end pipequick disconnect coupling clamp (8) (para 2.3.3.2).WARNINGPersonal injury may result from high pressure water if pressure relieve valve facesbutterfly valve. Ensure pressure relief valve is installed as shown in figure 2-16 toavoid personal injury.k. Install 6 inch pressure relief valve (11) on end of lateral grooved pipe fitting (9) with grooved-end pipequick disconnect coupling clamp (10) (para 2.3.3.2).2-46
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business