ELECTRICAL EQUIPMENT - Q.2
4.
Fault Finding on AC5
The AC 5 alternator is so designed that a flow of
current indicated either by the extinguishing of the
warning light, or as shown on the ammeter, is sufficient
evidence that the system is in proper working order.
Therefore, no open circuit, voltage or current output
checks
should
be
performed
on
the
installation
UNLESS:
(a) The warning light fails to illuminate when the
generator is stationary, and the switch is closed OR
fails to become extinguished when the alternator is
running.
(b) No charging current is shown on ammeter.
(c) The battery is flat.
(d) The battery is "boiling", indicating loss of voltage
control.
If any of the above symptoms occur, the procedure
indicated below should be followed.
(a) Connect a good quality moving coil voltmeter 0-50
volts range across the battery or regulator negative
terminal, and one of the three positive terminals
marked LO, MED, HI. Disconnect alternator output
terminal. Fit a good quality moving coil 0-100 amp
ammeter in series with the alternator terminal and
output lead. The battery should be in a charged
condition.
(b) Close the warning light switch (master electric switch
on dashboard) when the warning lamp should light
up.
(c) Switch on a 10-15 amperes load such as lights,
fans, etc., for fifteen minutes.
(d) Start engine and run at fast idle speed when
1.
The warning light should go out.
2.
The ammeter records a small charge dc-
pendant on engine speed.
(e) Increase engine speed momentarily to maximum
speed, when the charging current should be about
30 Amperes for 24 Volt, and 53 Amperes for 12 volt
systems.
(f)
With the alternator running at approximately half
speed, (engine speed about 1.500) rev/min) switch
off electrical load. Depending on the connection
selected for the positive sensing wire LO, MED or
HI, the voltage should rise to between 26 and 28
volts on 24 volt systems and 13-14 volts on 12 volt
systems and then remain constant. At the same
time the current reading should drop appreciably.
Any variance in the above data could indicate a fault
and the following procedure should be adopted before
disconnecting any components.
The regulator is a sealed unit and is non-repairable
and if found to be faulty it must be replaced.
Warning Lamp does not light up when switched
"On".
Check the bulb.
If no fault
Check all wiring connections at regulator, alternator
and battery.
If no fault
Switch off, disconnect F lead at regulator and
connect it to the negative terminal.
Switch on. If warning lamp lights up, the regulator is
faulty. If lamp fails to light up, the alternator is faulty.
Warning Lamp does not go out and Ammeter shows
no output when running.
Check
all
regulator,
alternator
and
battery
connections.
If no fault
Switch off, disconnect F lead at regulator and
connect to regulator negative terminal.
Switch on, and run at fast idle.
If no output, alternator is faulty.
If output appears, regulator is faulty.
Warning Lamp does not go out when running and
Ammeter shows reduced output with full output only
at maximum speed or Warning Lamp goes out but
Alternator delivers reduced output. Full output only
at maximum speed.
Alternator faulty. Remove from installation and
apply open circuit diode check.
Warning Lamp flashes intermittently and Ammeter
needle oscillates when Battery is fully charged and
no loads are switched in.
Check for excessive resistance in regulator negative
sensing lead.
If no fault, regulator is faulty.